Submersible Pump Preventive Maintenance Checklist

⚠️ Disclaimer: These tasks are guidelines only. They do not include lockout/tagout (LOTO), energy isolation, or other safety requirements. Review and verify suitability for your specific equipment and application. Add all required safety procedures per your company's policies and regulatory requirements before use. You are responsible for the safe and appropriate execution of all maintenance activities.


Submersible pumps fail from the outside in. The cable goes first, then the seals, then the motor — and most of it happens underwater where nobody is looking. By the time there's a symptom you can hear or see, the damage is already done.

This checklist covers preventive maintenance tasks for submersible pumps used in wet wells, sumps, and similar applications. It is written for both field technicians executing the PM and maintenance managers building or auditing the program.

For a broader look at pump PM strategy, start with the pump PM fundamentals your program needs.


How to Use This Checklist

Record findings with specificity — not checkboxes. "Cable insulation intact" tells you nothing a year from now. "Cable shows minor abrasion at conduit entry, no insulation breach, flagged for monitoring" tells you everything. The difference between a finding and a checkbox answer is whether someone could read it six months later and know what you actually saw.

Trend your measurements over time. A single megohmmeter reading means almost nothing. The same reading compared against three prior measurements means a great deal. If insulation resistance is dropping — even if it is still above 1 MΩ — that trajectory is the finding.

The field checklist covers the highest-consequence tasks for technicians executing the PM. The reference checklist is the full task library for managers building, auditing, or expanding the program.


Field Checklist — Critical Tasks


Visual Inspection Tasks

Task Freq Type
Inspect pump unit for visible damage, corrosion, or abnormal wear on housing, fittings, and cable entry seals. Every PM MEC
Check power cable and conduit for cuts, abrasion, kinking, or damaged insulation along the entire accessible run. Every PM ELE
Verify pump is seated correctly in the wet well or sump and that the guide rail system (if equipped) is properly aligned and undamaged. Every PM MEC
Inspect discharge piping, check valve, and unions for leaks, corrosion, or looseness. Every PM MEC

Mechanical Inspection Tasks

Task Freq Type
Clean intake screen/strainer of debris, rags, or buildup that may restrict flow. Every PM MEC
Check wet well or sump for excessive sludge accumulation that may impair pump operation or shorten service life. Quarterly MEC
Inspect and test high-level alarm float or sensor to verify alert activates at the correct level. Quarterly ELE

Operational Checks

Task Freq Type
Confirm float switches or level sensors are free-moving, properly positioned, and not tangled or fouled. Every PM ELE
Test pump operation through a manual start cycle — verify unit starts, runs smoothly, and stops on command without unusual noise or vibration. Monthly ALL

Electrical Inspection Tasks

Task Freq Type
Record amp draw on each phase during run cycle and compare to nameplate FLA. Flag any phase over 105% FLA. Monthly ELE
Inspect control panel — verify all indicators are normal, no fault codes displayed, and panel interior is dry and free of pests. Monthly ELE
Measure insulation resistance of power cable and motor windings with a megohmmeter. Record and trend. Minimum acceptable: 1 MΩ. Annually ELE

Reference Checklist — Full Task Library


Visual Inspection Tasks

Task Freq Type
Inspect pump housing, cable entry glands, and all exterior seals for signs of corrosion, physical damage, or deterioration. Note any areas where protective coating has failed. Every PM MEC
Inspect power cable for cuts, abrasion, kinking, heat damage, or compromised insulation along the full accessible run. Check cable strain relief at pump head and junction box. Every PM ELE
Verify pump is properly seated on guide rails or floor stand and that discharge coupling is fully engaged and not leaking. Every PM MEC
Inspect discharge piping, check valve, isolation valve, and all unions or flanges for leaks, corrosion, or wear. Every PM MEC

Mechanical Inspection Tasks

Task Freq Type
Inspect intake screen/strainer and impeller access — clean debris and note any evidence of rags, solids, or material that indicates process contamination or operational misuse. Every PM MEC
Inspect float switches and level sensors — confirm free movement, correct set-point positioning, and no fouling or tangling. Adjust if out of position. Every PM ELE
Check wet well or sump — assess sludge and debris accumulation level. If accumulation is impeding pump suction or float operation, coordinate a cleanout. Quarterly MEC
Inspect check valve operation — confirm valve seats completely on pump shutoff (no backflow/water hammer). If valve is accessible, inspect disc and seat for wear or debris. Quarterly MEC
Remove pump from wet well if accessible — inspect impeller for wear, erosion, or clogging. Inspect seal area for leakage or shaft wear. Reinstall and confirm proper seating. Annually MEC
Verify pump performance: compare current flow rate and discharge pressure to baseline or design specification. A significant drop may indicate impeller wear, seal bypass, or clogging. Annually MEC
Review run-hour log and pump cycle count. Assess against manufacturer's service interval for seal replacement, bearing inspection, or overhaul. Schedule service if threshold is approaching. Annually MEC
Confirm a matching spare pump or critical spare parts (impeller, mechanical seal, cable entry kit) are on hand. Update spare parts inventory if needed. Annually MEC

Operational Checks

Task Freq Type
Perform a manual start cycle. Verify unit starts without hesitation, runs smoothly, produces normal flow, and stops cleanly on command. Note any noise, vibration, or slow response. Monthly ALL

Electrical Inspection Tasks

Task Freq Type
Measure and record running amperage on all three phases during normal operation. Compare to nameplate FLA. Investigate and document any phase above 105% FLA or phase imbalance greater than 5%. Monthly ELE
Inspect control panel: no fault codes, indicator lights normal, contactors and terminals seated, panel interior dry and free of pests or moisture intrusion. Monthly ELE
Test high-level alarm float or sensor by manually raising float to trip point. Verify alarm activates and resets correctly. Document test result. Quarterly ELE
Measure insulation resistance of motor windings and power cable using a 500V or 1000V megohmmeter. Record phase-to-phase and phase-to-ground readings. Trend over time. Minimum acceptable: 1 MΩ; investigate if trending downward. Semi-Annually ELE
Inspect thermal overload and overcurrent protection settings in control panel. Verify trip setpoints are correct for the installed motor FLA. Semi-Annually ELE
Inspect all electrical terminations at control panel, junction box, and motor connection head. Re-torque loose terminals. Look for discoloration, oxidation, or arcing marks. Annually ELE

Failure Modes This Checklist Targets

Cable insulation failure. The power cable runs through wet, abrasive environments. Cuts, kinking, and degraded insulation create ground faults that take out the motor without warning. The cable inspection and megohmmeter tasks catch this while there is still time to act.

Motor winding failure from moisture ingress. When cable entry seals fail or the pump motor casing is compromised, moisture reaches the windings. Insulation resistance trending is the only way to catch this failure mode before it becomes a rewind or a replacement.

Impeller wear and clogging. Rags, solids, and debris erode impellers and reduce flow. A pump that is moving less fluid than it should may still be running — it is just failing slowly. Performance verification and strainer inspection are the check.

Float and sensor fouling. In dirty sump environments, float switches get tangled, coated, and stuck. A pump that can't respond to its level sensor will either run dry or let the wet well overflow. Float inspection every PM is non-negotiable.

Check valve failure and backflow. A check valve that doesn't seat properly lets the discharge column reverse on shutoff. That means water hammer, impeller stress, and a pump that has to fight its own backflow every time it starts. Quarterly valve inspection catches this before it shortens bearing and seal life.

High-level alarm failure. The alarm exists for one reason — to tell someone the pump isn't keeping up before the sump overflows. If the alarm float is fouled or the setpoint has drifted, you don't have a backup. You have a false sense of security.


Related Checklists

Featured Products